首页> 外文期刊>Journal of Thermal Science and Engineering Applications: Transactions of the ASME >Simulation-Based Assessment of Performance Indicator for Data Center Cooling Optimization
【24h】

Simulation-Based Assessment of Performance Indicator for Data Center Cooling Optimization

机译:基于仿真的数据中心冷却优化性能指标评估

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Data center power consumption has grown substantially in the past 20 years. According to the United States Data Center Energy Usage Report, the data center consumption in 2014 was estimated at 70 billion kWh, which accounted for 1.8% of the total U.S. electricity. The present effort investigates the effects of various data center parameters on a new set of metrics called the performance indicator to help assess and optimize the cooling performance of data centers. The three metrics in the performance indicator include power usage effectiveness ratio (PUEr), thermal conformance, and thermal resilience. The data center parameters investigated include computer room air handler (CRAH) setpoints, room configuration layouts, and containment strategies. The results show that the CRAH setpoint significantly influences the PUEr with higher setpoint values resulting in lower PUEr values. Room configuration layout changes and containment strategies showed substantial effects on thermal conformance and thermal resilience. The thermal conformance was increased approximately 10% with room configuration changes without changing the PUEr. Full hot aisle containment also improved the thermal conformance by 7.4%.
机译:数据中心功耗在过去的20年里大幅增加。根据美国数据中心能源使用报告,2014年的数据中心消费量估计为700亿千瓦时,占美国电力总额的1.8%。本努力调查了各种数据中心参数对一个名为“性能指标”的新度量标准的影响,以帮助评估和优化数据中心的冷却性能。性能指标中的三个指标包括电力使用效率(PUER),热量符合和热弹性。调查的数据中心参数包括计算机室空气处理程序(CRAH)设定值,房间配置布局和密封策略。结果表明,CRAH设定点显着影响PUE,具有更高的普及值较低的普及值。房间配置布局变化和遏制策略对热符合和热弹性显示出大量影响。热量符合性增加约10%,房间配置变化而不改变PUER。全热过道遏制也提高了热量一致性7.4%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号