摘要

Cooling towers have the potential to develop infectious concentrations of Legionella pneumophila.Legionella counts increases where biofilm and warm water temperatures are present.In this study,biofilm associated L.pneumophila and heterotrophic bacteria were compared in terms of material dependence.Model cooling tower system was experimentally infected by L.pneumophila standard strain and monthly monitored.Different materials were tested for a period of 180 days.The lowest L.pneumophila and heterotrophic plate counts were measured on plastic polymers,whereas L.pneumophila and heterotrophic bacteria were accumulated rapidly on galvanized steel surfaces.It can be concluded that selection of plastic polymers,as a manufacturing material,are suitable for recirculating water systems.
机译:冷却塔可能会增加肺炎军团菌的感染浓度。存在生物膜和温水的地方,军团菌数量会增加。在这项研究中,对生物膜相关的嗜肺军团菌和异养细菌的材料依赖性进行了比较。用肺炎链球菌标准菌株进行实验性感染并每月监测。对不同材料进行180天的测试。在塑料聚合物上测定了最低的肺炎链球菌和异养菌板数,而在镀锌的情况下,肺炎衣原体和异养菌迅速积聚。可以得出结论,选择塑料聚合物作为制造材料适用于循环水系统。