首页> 外文会议>2016 Down to Earth Conference >Power system earthing – its commissioning and test errors
【24h】

Power system earthing – its commissioning and test errors

机译:电力系统接地–调试和测试错误

获取原文
获取原文并翻译 | 示例

摘要

This paper is a case study of an earthing system commissioning test, the associated errors and how to compensate for them. When measuring the impedance of an earth grid it is important to realise that there are many factors that can influence the test results. Inductive coupling between the current lead and remote earth lead and not being at remote soil potential are such factors that must be considered when determining the earth grid impedance. Often, errors due to inductive and conductive coupling are unavoidable because of the layout of the test circuit and the size of the earthing system or existence of MEN, transmission or distribution power lines, etc. For this reason, computer modelling is essential to correct interactions between the test circuit and earth grid under test, and interactions within the test circuit itself.
机译:本文是一个接地系统调试测试,相关错误以及如何进行补偿的案例研究。在测量接地网的阻抗时,重要的是要意识到有很多因素会影响测试结果。在确定接地网阻抗时,必须考虑电流引线与远地引线之间的电感耦合,而不是处于远处的土壤电势。通常,由于测试电路的布局和接地系统的大小或MEN,传输或配电电源线等的存在,不可避免地会由于电感和导电耦合而产生错误。因此,计算机建模对于纠正交互作用至关重要测试电路和被测接地网格之间的关系,以及测试电路本身内部的相互作用。