首页> 美国政府科技报告 >Comparison of Ceiling Jet Temperatures Measured in an Aircraft Hanger Test Firewith Temperatures Predicted by the DETACT-QS and LAVENT Computer Models
【24h】

Comparison of Ceiling Jet Temperatures Measured in an Aircraft Hanger Test Firewith Temperatures Predicted by the DETACT-QS and LAVENT Computer Models

机译:在飞机吊架试验中测量的天花板射流温度的比较火灾与DETaCT-Qs和LaVENT计算机模型预测的温度

获取原文

摘要

Predictions of the DETACT-QS and LAVENT computer fire models are compared totemperature measurements made during the calibration of the fire detection system in a military aircraft hanger. Two 3.34 sq m isopropyl alcohol pool fire tests 60 second duration were conducted in the 37 m by 40 m by 14 m high main hanger bay. Brass disks with a known thermal response time index (RTI) were used to simulate the thermal element in a sprinkler or heat detector. Measurements were made of centerline plume temperatures, and ceiling jet gas and disk temperatures at radial distances of 0, 2.7, 5.5, 8.2, and 11.0 m from the centerline of the fire, 380 mm below the ceiling. At a radial distance of 5.5 m, measurements of ceiling jet gas temperatures were also made 150 and 610 mm below the ceiling. Comparisons of predictions and measurements demonstrate some of the strengths and weakness of DETACT-QS and LAVENT for the fire scenario.