High-temperature superconducting (HTS) transformers promise decreased weight and volume and higher efficiency. A 1 MVA HTS railway transformer was built and tested at Siemens AG. This paper deals with the prediction of ac loss in the BSCCO/Ag-tape windings. In a railway transformer the tape carries ac current in alternating field, the temperature differs from 77 K, tapes are stacked or cabled and overcurrents and higher harmonics occur. In ac-loss literature these issues are treated separately, if at all. We have developed a model that predicts the ac loss in sets of BSCCO/Ag-tape coils, and deals with the above-mentioned issues. The effect of higher harmonics on the loss in HTS tapes is considered for the first time. The paper gives a complete overview of the model equations and required input parameters. The model is validated over a wide range of the input parameters, using the measured critical current and ac loss of single tapes, single coils and sets of coils in the 1 MVA transformer. An accuracy of around 25 percent is achieved in all relevant cases. Presently the model is developed further, in order to describe other HTS materials and other types of applications.
机译:高温超导(HTS)变压器有望减轻重量和体积,并提高效率。西门子股份公司制造并测试了1 MVA HTS铁路变压器。本文讨论了BSCCO / Ag-tape绕组中交流损耗的预测。在铁路变压器中,磁带在交流电场中承载交流电流,温度不同于77 K,磁带被堆叠或电缆连接,并且产生过电流和高次谐波。在流失文献中,这些问题(如果有的话)将单独处理。我们已经开发出一种模型,该模型可以预测BSCCO / Ag胶带线圈组中的交流损耗,并解决上述问题。首次考虑了高次谐波对HTS磁带损耗的影响。本文提供了模型方程式和所需输入参数的完整概述。该模型在1 MVA变压器中使用单个磁带,单个线圈和一组线圈的实测临界电流和交流损耗,在各种输入参数范围内进行了验证。在所有相关情况下,精度均达到25%。目前,该模型正在进一步开发,以描述其他HTS材料和其他类型的应用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号