首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Performance analyses of novel two-phase ejector enhanced multi-evaporator refrigeration systems
【24h】

Performance analyses of novel two-phase ejector enhanced multi-evaporator refrigeration systems

机译:新型两相喷射器增强型多蒸发器制冷系统的性能分析

获取原文
获取原文并翻译 | 示例
           

摘要

In the present study, four novel layouts (namely EECRS1, EECRS2, EECRS3 and EECRS4) of three evaporator two-stage compression refrigeration system have been proposed using double two-phase ejectors. Thermodynamic analysis and ejector area ratio optimization have been done to study the effects of cycle operating temperature and evaporator load distribution on the cycle and ejector performance parameters. Performance comparisons with basic valve expansion two-stage compression, ejector enhanced single-stage compression and basic valve expansion single-stage compression three evaporator refrigeration systems are presented as well. Study shows that for typical combination of air-conditioning (5 degrees C), refrigeration (-20 degrees C) and freezing (-40 degrees C) applications, proposed refrigeration cycles yield the COP enhancement of about 20% compared to basic valve expansion two-stage compression, 67% compared to ejector enhanced single-stage compression and 117% compared to basic valve expansion single-stage compression system. Volumetric cooling capacity also improves significantly. Within proposed layouts, EECRS4 is most efficient; however, the operation is more challenging than others. Simulation results also reveal that the performance improvement is more sensitive with cooling load distribution compared to operating temperature. Present study may serve as a good guideline for promising use of ejector in three-evaporator system. (C) 2016 Elsevier Ltd. All rights reserved.
机译:在本研究中,已经提出了使用双两相喷射器的三个蒸发器两级压缩制冷系统的四个新颖的​​布局(即EECRS1,EERCS2,EERCS3和EECRS4)。已经进行了热力学分析和喷射器面积比优化,以研究循环工作温度和蒸发器负荷分布对循环和喷射器性能参数的影响。还介绍了基本阀膨胀两级压缩,喷射器增强型单级压缩和基本阀膨胀单级压缩三个蒸发器制冷系统的性能比较。研究表明,对于空调(5摄氏度),制冷(-20摄氏度)和冷冻(-40摄氏度)的典型组合,与基本阀门膨胀相比,建议的制冷循环使COP提升约20%。级压缩,与喷射器增强型单级压缩相比为67%,与基本阀膨胀单级压缩系统相比为117%。容积冷却能力也显着提高。在建议的布局中,EECRS4的效率最高。但是,该操作比其他操作更具挑战性。仿真结果还显示,与工作温度相比,性能改进对冷却负荷分布更为敏感。目前的研究可以为在三蒸发器系统中使用喷射器提供良好的指导。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号