首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Application of pump-assisted separate heat pipe on dehumidifying enhancement in air conditioning system
【24h】

Application of pump-assisted separate heat pipe on dehumidifying enhancement in air conditioning system

机译:泵辅助热管在空调系统除湿中的应用

获取原文
获取原文并翻译 | 示例
           

摘要

A study was carried out to investigate the effect of pump-assisted separate heat pipe (PASHP) on energy consumption and dehumidifying enhancement in the air conditioning system. In the experiment, four sets of PASHP filled into R134a as the working fluid were constructed. when the number of PASHP employed in the system changes from 0 to 4 sets at the constant inlet air state of 28.5 degrees C and 60% relative humidity, the apparatus dew point falls from 11.7 degrees C to 8.2 degrees C, the supply air temperature rises from 11.7 degrees C to 24.1 degrees C, while dehumidifying capacity of the system has ultimately increased by 29.5%. The index 13 (ratio between the cooling energy saved by PASHP and the total cooling capacity of the air cooling system with PASHP) is 40.4%, and the index 8 (ratio between the cooling energy saved by PASHP and the cooling capacity of the air conditioner's evaporator) is 66.0%. The study indicates that the air conditioning system employed with PASHP can significantly reduce its energy consumption and improve its dehumidifying capacity. (C) 2015 Elsevier Ltd. All rights reserved.
机译:进行了一项研究,以研究泵辅助独立热管(PASHP)对空调系统的能耗和除湿效果的影响。在实验中,构造了四套PASHP作为工作流体填充到R134a中。当在28.5摄氏度和60%相对湿度的恒定进气状态下,系统中使用的PASHP数量从0变为4组时,设备露点从11.7摄氏度降至8.2摄氏度,送风温度升高从11.7摄氏度到24.1摄氏度,而系统的除湿能力最终提高了29.5%。指数13(PASHP节省的冷却能量与装有PASHP的空气冷却系统的总冷却能力之比)为40.4%,而指数8(PASHP节省的冷却能量与空调器的制冷能力之比)蒸发器)为66.0%。研究表明,与PASHP一起使用的空调系统可以显着降低其能耗并提高其除湿能力。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号