A water system, consisting of several water mist nozzles, has been installed in a reduced-scale tunnel. Its effectiveness in blocking fire-induced smoke and heat is tested, with and without longitudinal ventilation. A total of 14 fire tests have been carried out, with 250 ml methanol in an iron tray (25 cm x 20 cm) as fuel. Temperatures have been measured by 30 thermocouples, located upstream and downstream of the fire location. The aim is to assess the effectiveness of the water system in preventing smoke spread and in reducing the temperature in the tunnel. Interaction of the water with the fire is avoided. The impact of water pressure, ventilation velocity and nozzle arrangement on the effectiveness in smoke blocking and temperature reduction is discussed. The result confirms that the water system effectively reduces the temperatures and prevents smoke spreading in the absence of longitudinal ventilation. However, strong longitudinal ventilation (0.8 m/s ventilation velocity in the reduced-scale tunnel, corresponding to critical velocity in full-scale (1:10) tunnel) reduces the effectiveness in blocking the smoke spreading by the water system, although the temperature reduction downstream the water system remains in place. Higher water pressure makes the cooling effect stronger, because more and smaller water droplets are injected into the tunnel. For a given level of water pressure level, the impact of the nozzle row configuration is small in the tests. (C) 2016 Elsevier Ltd. All rights reserved.
机译:在缩小规模的隧道中安装了由几个水雾喷嘴组成的水系统。在纵向通风和不纵向通风的情况下,均测试了其在阻止火源烟雾和热量方面的有效性。总共进行了14次燃烧测试,用铁托盘(25 cm x 20 cm)中的250 ml甲醇作为燃料。温度是由位于火场上游和下游的30个热电偶测得的。目的是评估水系统在防止烟雾扩散和降低隧道温度方面的有效性。避免了水与火的相互作用。讨论了水压,通风速度和喷嘴布置对阻烟和降温效果的影响。结果证实,在没有纵向通风的情况下,水系统可有效降低温度并防止烟气扩散。但是,尽管温度较高,但强烈的纵向通风(缩小规模的隧道中的通风速度为0.8 m / s,对应于满比例(1:10)隧道中的临界速度)会降低阻止水系统传播烟雾的有效性。减少下游水系统仍然存在。更高的水压使冷却效果更强,因为越来越多的水滴被注入隧道中。对于给定的水压水平,在测试中,喷嘴排结构的影响很小。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号