首页> 外文期刊>日本建築学会環境系論文集 >実戸建住宅における空気分配および温熱環境とエネルギー消費に関する検証: 住宅における床チャンバー空調の設計法に関する研究 その4
【24h】

実戸建住宅における空気分配および温熱環境とエネルギー消費に関する検証: 住宅における床チャンバー空調の設計法に関する研究 その4

机译:验证独立式住宅中的空气分布,热环境和能耗:房屋中的地板室空调设计方法研究第4部分

获取原文
获取原文并翻译 | 示例
       

摘要

The authors have proposed an air conditioning system utilizing under-floor chambers and currently available commodity products such as domestic electric air conditioners. In an existing detached house which is highly insulated and equipped with the system, the measurements were carried out. The air distribution of the system was measured. Furthermore temperature and electric power consumption have been measured over three years. .The air distribution was reasonable, the temperature was moderate and the difference among the rooms was very small, and primary energy consumption was lower than the criterion of the energy standard in Japan. Thus the air-conditioning system was verified.%床チャンバーを用いた全館空調が導入された住宅において実測を行ったところ次の点が明らかとなった。①送風ファンの風量の設定を変化させると,全体の循環風量や吹出口の風量バランスが変化した。よって,送風ファンの設定によって風量や風量バランスの制御が可能であった。②レターン温度は,暖房時20〜21°C,冷房時27〜28°Cであり,ほぼ目標温度に制御されていた。室間温度差は最大1℃程度で一般的な住宅に比べてかなり小さくなつた。レターンの相対湿度は,冷房時50〜70%程度,暖房時25〜40%程度であり,特に暖房時は湿度制御が十分ではなかった。
机译:作者提出了一种利用地板下腔室和当前可用商品如家用电动空调的空调系统。在一个高度绝缘并装有该系统的现有独立式住宅中,进行了测量。对该系统进行了测量,并测量了三年的温度和电力消耗,空气分配合理,温度适中,房间之间的差异很小,一次能源消耗低于该标准。因此,对空调系统进行了验证。%当在引入了使用地板室的空调系统的房屋中进行实际测量时,以下几点变得很清楚。 (1)改变鼓风机的风量设置时,总循环风量和出口处的风量平衡发生变化。因此,可以通过设置鼓风机来控制风量和风量平衡。 (2)加热时的返回温度为20〜21℃,冷却时的返回温度为27〜28℃,被控制为大致目标温度。最大的室温差约为1°C,这比典型的房屋要小得多。回流时的相对湿度在冷却期间约为50至70%,在加热期间约为25至40%,尤其是在加热期间,湿度控制不足。