首页> 外文期刊>IEEE Transactions on Power Delivery >Analysis of Electric Field, Ion Flow Density, and Corona Loss of Same-Tower Double-Circuit HVDC Lines Using Improved FEM
【24h】

Analysis of Electric Field, Ion Flow Density, and Corona Loss of Same-Tower Double-Circuit HVDC Lines Using Improved FEM

机译:用改进的有限元方法分析同塔双回路高压直流输电线路的电场,离子流密度和电晕损耗

获取原文
获取原文并翻译 | 示例
           

摘要

This letter analyzes the ion flow field of the emerging same-tower double-circuit HVDC lines using an improved method. The improved method is based on SUPG FEM, which is more accurate than the widely applied upwind FEM. It is shown that the SUPG FEM results agree better with the measured data than the upwind FEM results. Reason for the upwind FEM's inaccuracy is given. Using the SUPG FEM, the influences of same-tower double-circuit HVDC lines' parameters on corona loss, ground-level maximum electric field, and ion flow density are analyzed.
机译:这封信使用一种改进的方法分析了新兴的同塔双回高压直流输电线路的离子流场。改进的方法基于SUPG有限元,它比广泛应用的迎风有限元法更准确。结果表明,SUPG有限元结果与测得的数据比逆风FEM结果更好。给出了上风FEM不准确的原因。使用SUPG有限元,分析了同塔双回HVDC线路参数对电晕损耗,地面最大电场和离子流密度的影响。