The Application of Correlation Technique in Detecting Internal and External Faults in Three-Phase Transformer and Saturation of Current Transformer

机译:相关技术在三相变压器内部和外部故障检测及电流互感器饱和中的应用

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

A new technique based on correlation coefficients analysis of current waveforms is used to detect an internal fault that occurs in a three-phase transformer as well as to distinguish it from external faults. The technique depends on the changes in current waveforms that occur during the faults. Autocorrelation has been added to cross-correlation in one scheme for better fault discrimination and to increase speed in detecting the fault within a very short time. The proposed algorithm is so fast that it is able to detect faults within less than 3 ms. The technique also overcomes the problem of the current transformer's saturation, which is considered one of the biggest problems in protection methods especially in differential protection. The new algorithm was tested practically and the results were processed using the LabVIEW and MATLAB programmes. The practical test results show that the internal faults, particularly an interturn fault type with only two turns, are shorted and can be detected and correctly identified from the external fault.
机译:一种基于电流波形相关系数分析的新技术被用来检测三相变压器中发生的内部故障,并将其与外部故障区分开。该技术取决于故障期间发生的电流波形变化。在一种方案中,自相关已添加到互相关中,以实现更好的故障判别并提高在非常短的时间内检测故障的速度。所提出的算法是如此之快,以至于它能够在不到3 ms的时间内检测到故障。该技术还克服了电流互感器饱和的问题,该问题被认为是保护方法(尤其是差动保护)中最大的问题之一。新算法经过了实际测试,结果使用LabVIEW和MATLAB程序进行了处理。实际测试结果表明,内部故障(特别是仅两匝的匝间故障类型)短路,可以从外部故障中检测并正确识别。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号