This study presents a methodology that allows examining the differential protection of power transformers through computational simulations and numerical relay tests. Using that purpose, the alternative transient program (ATP) was used as a computational tool to perform several different events, which the power transformers are submitted to, and that can cause mal-operation of its differential protection, such as: external and internal faults, inrush current and saturation of current transformers (CTs). A testing system was implemented in laboratory, which consisted in simulating the power system in ATP (power transformer, CTs and faults modes) and applying the simulated signals through a programmable test set to a commercial relay to evaluate their response to these events. The main results of the behaviour of transformer protection relay under the tested transients are presented and discussed in this work.
机译:这项研究提出了一种方法,可以通过计算仿真和数字继电器测试来检查电力变压器的差动保护。出于此目的,备用瞬态程序(ATP)用作计算工具来执行几个不同的事件,这些事件将被提交给电力变压器,并可能导致其差动保护出现故障,例如:内部和外部故障,浪涌电流和电流互感器(CT)的饱和度。在实验室中实施了一个测试系统,该系统包括以ATP(电源变压器,CT和故障模式)模拟电源系统,并通过可编程测试装置将模拟信号应用于商用继电器,以评估其对这些事件的响应。在此工作中,将介绍并讨论在测试瞬变条件下变压器保护继电器的行为的主要结果。