Thermal Control Strategies for Reliable and Energy-Efficient Data Centers

机译:可靠且节能的数据中心的热控制策略

获取原文
获取原文并翻译 | 示例
           

摘要

Two self-developed control schemes, ON/OFF and supervisory control and data acquisition (SCADA), were applied on a hybrid evaporative and direct expansion (DX)-based model data center cooling system to assess the impact of controls on reliability and energy efficiency. These control schemes can be applied independently or collectively, thereby saving the energy spent on mechanical refrigeration by using airside economization and/or evaporative cooling. Various combinations of system-level controls and component-level controls are compared to a baseline no-controls case. The results show that reliability is consistently met by employing only sophisticated component-level controls. However, the recommended conditions are met approximately 50% of the simulated time by employing system-level controls only (i.e., SCADA) but with a reduction in data center cooling system power usage effectiveness (PUE) values from 3.76 to 1.42. Moreover, the recommended conditions are met at all averaged times with an even lower cooling system PUE of 1.13 by combining system-level controls only (SCADA and ON/OFF controls). Thus, the study introduces a simple method to compare control schemes for reliable and energy-efficient data center operation. The work also highlights a potential source of capital expenses and operating expenses savings for data center owners by switching from expensive built-in component-based controls to inexpensive, yet effective, system-based controls that can easily be imbedded into existing data center infrastructure systems management.
机译:在基于混合蒸发和直接膨胀(DX)的模型数据中心冷却系统上应用了两种自行开发的控制方案ON / OFF和监督控制与数据采集(SCADA),以评估控制对可靠性和能效的影响。这些控制方案可以独立应用,也可以集中应用,从而通过节省空气和/或蒸发冷却来节省机械制冷所需的能源。将系统级控件和组件级控件的各种组合与基准无控件的情况进行了比较。结果表明,仅采用复杂的组件级控件即可始终满足可靠性要求。但是,仅通过采用系统级控件(即SCADA),可以满足建议条件的大约50%的模拟时间,但数据中心冷却系统的电源使用效率(PUE)值从3.76降低到1.42。此外,通过仅组合系统级控件(SCADA和ON / OFF控件),在所有平均时间均满足建议的条件,并且冷却系统PUE更低,为1.13。因此,本研究引入了一种简单的方法来比较控制方案的可靠性和节能数据中心的运行。这项工作还突出显示了数据中心所有者的潜在资本支出和运营支出节省来源,方法是从昂贵的内置基于组件的控件切换到廉价但有效的基于系统的控件,这些控件可以轻松地嵌入到现有数据中心基础架构系统中管理。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号