首页> 外文期刊>Generation, Transmission & Distribution, IET >Development of online monitoring system for 1500 V ethylene-propylene-rubber DC feeder cable of Shanghai urban rail transit
【24h】

Development of online monitoring system for 1500 V ethylene-propylene-rubber DC feeder cable of Shanghai urban rail transit

机译:上海城市轨道交通1500 V乙丙橡胶直流馈线电缆在线监测系统的开发

获取原文
获取原文并翻译 | 示例
           

摘要

The form of ethylene-propylene-rubber DC feeder cable faults can be attributed to insulation aging and mechanical insulation crack, while integrating the DC leakage current (DLC) signal, and track discharge (TD) signal could effectively detect such defaults online. Further research results about an online monitoring system will be introduced, which is developed to evaluate the insulation of DC feeder cable in the traction substation of the Shanghai urban rail transit. The monitoring system adopts distributed structure and is made up of TD sensors, DLC sensors, data acquisition system and monitoring central with faulty diagnosis expert system. The experiments were carried out, both under the condition that the insulation of the DC feeder cables is in the good and fault status, in the laboratory, respectively, to verify the feasibility of the system. The results indicated that the system can forecast the insulation aging fault and the crack fault of the feeder cable. Furthermore, the system was also installed in the field and put in the real operation and it run stably and reliably in the field, and the diagnostic results were consistent with the actual circumstances.
机译:乙丙橡胶直流馈线电缆故障的形式可以归因于绝缘老化和机械绝缘裂纹,同时对直流泄漏电流(DLC)信号和轨迹放电(TD)信号进行积分可以有效地在线检测到此类默认值。将介绍有关在线监视系统的进一步研究结果,该系统将用于评估上海城市轨道交通牵引变电站中直流馈线电缆的绝缘性。监控系统采用分布式结构,由TD传感器,DLC传感器,数据采集系统和具有故障诊断专家系统的中央监控系统组成。在直流馈线电缆的绝缘处于良好状态和故障状态的条件下,分别在实验室中进行了实验,以验证该系统的可行性。结果表明,该系统可以预测馈线电缆的绝缘老化故障和裂纹故障。此外,该系统还安装在现场并投入实际运行,在现场稳定可靠运行,诊断结果与实际情况相吻合。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号