首页> 外文期刊>Fuel >Mercury re-emission from adipic acid enhanced FGD absorber - Full scale investigations on ~ 400 MW_e boiler (lignite) with oxidant injection to flue gas
【24h】

Mercury re-emission from adipic acid enhanced FGD absorber - Full scale investigations on ~ 400 MW_e boiler (lignite) with oxidant injection to flue gas

机译:己二酸增强的烟气脱硫吸收塔中的汞再排放-〜400 MW_e锅炉(褐煤)的氧化剂注入烟气的大规模研究

获取原文
获取原文并翻译 | 示例
           

摘要

The paper presents the results of an industrial scale study of mercury re-emission phenomenon from the flue gas desulphurization (FGD) absorber that purifies the lignite combustion gases. The available research results on re-emission phenomena at a laboratory and pilot scale were reviewed and verified in full scale conditions. It was confirmed that the phenomenon of re-emission is dependent on the FGD absorber operating conditions (pH, ORP) and the concentration of adipic acid in the sorption solution. Based on the conducted tests it was found that proper regulation of the FGD absorber's operating parameters can significantly reduce Hg-0 re-emission to the atmosphere. The interesting phenomenon was observed during the test, when the oxidant was fed to flue gas (X 0.75) and average values of ORP 140 mV and pH 6.0 a large amount of Hg-T was released from tested FGD absorber to atmosphere (up to 200 mu g/m(3) ).
机译:本文介绍了工业规模研究结果,该研究结果来自净化褐煤燃烧气体的烟气脱硫(FGD)吸收器中的汞再排放现象。在实验室和中试规模上可获得的有关再排放现象的研究结果已在全面条件下进行了审查和验证。已确认再发射现象取决于FGD吸收器的工作条件(pH,ORP)和吸附溶液中己二酸的浓度。根据进行的测试,发现对烟气脱硫吸收器的运行参数进行适当的调节可以显着减少Hg-0向大气的再排放。在测试过程中观察到有趣的现象,当氧化剂被送入烟道气(X> 0.75)且ORP <140 mV和pH <6.0的平均值时,大量的Hg-T从被测试的FGD吸收器释放到大气中(高达200μg / m(3))。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号