首页> 外文期刊>Fire Technology >Hold Time Calculations for Non-Standard Enclosures
【24h】

Hold Time Calculations for Non-Standard Enclosures

机译:非标准机箱的保持时间计算

获取原文
获取原文并翻译 | 示例
           

摘要

Current methods of calculating hold time for a fire fighting gas assume that the enclosure is of uniform horizontal cross-sectional area and has horizontal upper and lower boundaries (a standard enclosure). The paper shows that the hold time equation for continuous mixing in standard enclosures may also be used for non-standard enclosures, presents exact and simplified equations for descending interfaces in non-standard enclosures, and discusses the accuracy of the simplified equation. Considering the error when the simplified equation is applied to standard enclosures, and that it is always conservative for an enclosure of any shape, it is suggested that it may be used as an approximation for non-standard enclosures. The paper also presents a hold time equation for a descending interface in a standard enclosure with laminar flow in the leaks.
机译:当前计算灭火气体的保持时间的方法假定外壳的水平横截面面积均匀,并且具有水平的上下边界(标准外壳)。本文表明,在标准机柜中连续混合的保持时间方程式也可用于非标准机柜,它为非标准机柜中的下降接口提供了精确的简化方程,并讨论了简化方程的准确性。考虑到简化方程应用于标准外壳时的误差,并且对于任何形状的外壳始终是保守的,因此建议将其用作非标准外壳的近似值。本文还提出了标准外壳中下降界面的保持时间方程,其中泄漏处有层流。