首页> 美国卫生研究院文献>Sensors (Basel Switzerland) >Measurements of Impedance and Attenuation at CENELEC Bands for Power Line Communications Systems
【2h】

Measurements of Impedance and Attenuation at CENELEC Bands for Power Line Communications Systems

机译:电力线通信系统CENELEC频段的阻抗和衰减测量

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Power line impedance is a very important parameter on the design of power line communications (PLC) modem architecture. Variations on the impedance of the power line affect the communications circuit performance. In order to determine impedance of the power lines, measurements were carried out in Turkey at frequencies ranging from 10 to 170 kHz, (CENELEC A,B,C,D bands). Measurements were conducted in three categories: rural, urban and the industrial power lines. Experimental results are presented in graphical form. The measured impedances were determined as 3-17 ohms, 1-17 ohms, and 1-21 ohms for rural, urban and the industrial lines, respectively. A set of the formulas between impedance and frequency are developed on the power lines using the regression analysis from the obtained empirical data. Signal attenuations on the power lines in the CENELEC band are also measured for rural, urban and industrial regions. Attenuation measurements are repeated for phase-neutral, phase-ground and the neutral-ground conductors. Signal attenuations are found to be 4-30 dB, for different power lines. To establish validity of obtained results for the design of PLC systems, the results are compared with previous investigations. The effects of some household appliances such as TV, PC, UPS, lighting and cooling systems on the impedances and the attenuations for power line communications systems are observed. Some suggestions and proposals are presented for PLC modem designers.
机译:电力线阻抗是电力线通信(PLC)调制解调器体系结构设计中非常重要的参数。电源线阻抗的变化会影响通信电路的性能。为了确定电源线的阻抗,在土耳其以10到170 kHz(CENELEC A,B,C,D频段)的频率进行了测量。测量分为三类:农村,城市和工业电力线。实验结果以图形形式表示。对于农村,城市和工业线路,测得的阻抗分别确定为3-17欧姆,1-17欧姆和1-21欧姆。使用获得的经验数据的回归分析,在电力线上建立了一组阻抗和频率之间的公式。还针对农村,城市和工业区域测量了CENELEC频带中电力线上的信号衰减。对相中性,相接地和中性接地导体重复进行衰减测量。对于不同的电源线,信号衰减为4-30 dB。为了确定所获得的结果对PLC系统设计的有效性,将结果与以前的研究进行了比较。观察到某些家用电器(例如电视,PC,UPS,照明和冷却系统)对电力线通信系统的阻抗和衰减的影响。为PLC调制解调器设计人员提供了一些建议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号