摘要

Based on the dynamic dielectric recovery process in the vacuum gaps in series, investigations were made on post-arc insulation state in double and multi-breaks operation in high voltage power system. From the research on the breakdown weak points in high voltage vacuum gaps, their turnout and distribution, some theoretic work were made to set up the models for describing the statistical property of multi-breaks vacuum circuit-breakers’ breakdown and post-arc re-strike, which can be used for explaining the mechanism of the improvement in the breaking capacity of multi-breaks units compared with that of single-break ones which have the same equivalent gap length. The advantages of vacuum breakers with multi-breaks are proposed.