首页> 中文期刊> 《环境保护(英文)》 >Indoor Air Quality Real-Time Monitoring Results of Pathology Department

Indoor Air Quality Real-Time Monitoring Results of Pathology Department

         

摘要

In this work, the objectives were to provide a scientific basis for environmental governance and to ensure staff health by real-time monitoring of indoor air quality of the pathology department. Using eagle eye environment monitor to make a real-time dynamic monitoring of the air quality of the pathological technical room for 30 days, the paper records the monitoring data of PM 2.5, PM 10, formaldehyde, CO2, total volatile organic compounds (TVOC) every day at Beijing time 3 a.m, 10 am, 1 pm, 4 pm, and 10 pm, and makes a summarization and analysis. The average value of CO2 concentration of the 5 time points is (0.05 ± 0.01)%, and each time point concentration are different (P 0.05);the average TVOC concentration of the 5 time points is (0.08 + 0.31) mg/m3. They are all different between the concentration at each time point (P 2 and NO are not checked out. Through the real-time online monitoring of the pathology room, we find that the formaldehyde concentration of different time periods is far more than the safety value standard, and the concentration of formaldehyde, CO2, PM 2.5, PM 10 and total volatile organic compound (TVOC) is different at different time periods, and the concentrations at working time are higher than the non-working time. We must take effective measures to control the concentration of harmful gases in order to ensure the staff’s health.