To research the fire peril arrival time and evacuation situation when fire extinguishing system fails, in this work Pyrosim and Pathfinder software were used to; simulate the spread of smoke and human evacuation in a university library in Nanjing during fires. Through the comparative analysis of the temperature, smoke layer height, the visibility, CO concentration and FED value, the simulation results show that, the risk time of the library is 280s, on the fire scale of 4MW; the risk time of reading room is 125s, on the fire scale of 8MW. The evacuation simulation results indicate that the evacuation time of the entire library and reading room is 411s and 165s respectively. Finally, the fire safety of the library is evaluated by comparing the risk time and evacuation time. It is concluded that the exit of each layer is the first to reach the dangerous state; the direction of the hazardous area is also the direction of safe evacuation. The risk time of the library and the reading room, is the time when the height of smoke down to 2m. Therefore, the staff activity height, smoke volume and detection alarm and other factors, should be considered in the system design of smoke control.
机译:为了研究消防危险到达时间和疏散情况当灭火系统发生故障时,在这项工作中,Pyrosim和Pathfinder软件用于;在火灾期间,模拟南京大学图书馆的烟雾和人类疏散的传播。通过对温度,烟雾层高度,可见性,CO浓度和馈电值的比较分析,仿真结果表明,图书馆的风险时间为280s,在4mW的火量表上;阅读室的风险时间为125岁,火灾量为8MW。疏散仿真结果表明,整个图书馆和阅览室的疏散时间分别为411s和165s。最后,通过比较风险时间和疏散时间来评估图书馆的防火安全。结论是,每层的出口是第一个到达危险状态的;危险区域的方向也是安全疏散的方向。图书馆和阅览室的风险时间是烟雾高达2米的时间。因此,在烟雾控制系统设计中应考虑员工活动高度,烟雾体积和检测报警等因素。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号