Distributed generation (DG) including small hydro generation, solar PV generation and bio energy installed in a certain distribution network area has led to a condition which power generation by DG within the distribution network is more than the local consumption. The condition where DG generation has excess and power flows from the distribution network back to the grid is referred as Reverse Power Flow (RPF). In this paper, an analysis of RPF has been conducted focusing on a selected distribution network with a total capacity of 20MW mini-hydro generation installed to the substation. By utilizing DigSilent simulation software, a base case study has been analyzed and a base case simulation network model was then validated by comparing the simulation results with the historical data from SCADA. Based on the validated network simulation model, several case scenarios have been studied where the capacity of the installed DG into the distribution network were increased. The impact of RPF on voltage profile at 11kV bus, transformer tap change occurrence, transformer losses and distribution network losses has been analyzed in all scenarios and the results were then presented.
机译:包括小型水力生成(DG)的分布式发电(DG)安装在某个分销网络区域中的SOLAR PV生成和生物能量,导致了DG在配送网络内的发电的条件超过局部消耗。 DG生成从分发网络返回网格的电源流量的条件被称为反向功率流(RPF)。在本文中,已经对RPF进行了专注于所选择的分销网络,总容量为20MW迷你水电,安装到变电站。通过利用DigSilent仿真软件,已经分析了基本情况研究,然后通过将模拟结果与SCADA的历史数据进行比较来验证基本情况仿真网络模型。基于验证的网络仿真模型,已经研究了几种情况场景,其中安装的DG进入分销网络的容量增加。在所有场景中分析了RPF在11kV总线上的电压曲线上的影响,变压器抽头变化发生,变压器损耗和分配网络损耗,然后呈现结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号