In this paper a measuring system is presented to determine the frequency dependent transmission behaviour of high current instrument transformers (HCTs). Due to its high requirements, several components have been specially designed. These special requirements and the applied technical solutions are presented in this paper. Power amplifiers generate currents with a frequency range up to 40 kHz. The magnitudes of the generated currents are stepped up by using special transformers. A rigid Rogowski coil measures primary current and a shunt is used to measure the secondary current of the HCT to determine its frequency response. A special calibration concept of the used Rogowski coil and shunt ensure high accuracy (0.1%) of the measuring system in a frequency range up to 40 kHz. Test measurements at a HCT with a rated primary current of 8 kA show the capability of the measuring system.
机译:在本文中,提出了一种测量系统以确定高电流仪器变压器(HCT)的频率相关传输行为。由于其高要求,有些组件专门设计。本文提出了这些特殊要求和应用的技术解决方案。功率放大器产生高达40 kHz的频率范围的电流。使用特殊变压器加强产生电流的幅度。刚性Rogowski线圈测量初级电流和分流器用于测量HCT的二次电流以确定其频率响应。使用的Rogowski线圈的特殊校准概念和分流器确保高精度(0.1%)在高达40 kHz的频率范围内的测量系统。 HCT的测试测量,具有8 ka的额定初级电流,显示了测量系统的能力。