The corrosion failure analysis of the brass tube in a power plant condenser was conducted by the methods of chemical composition analysis, macro morphology inspection of the leakage point, metallurgical examination, scanning electron microscope and energy spectrum analysis etc. The results indicated that the failure of the brass tube was due to the erosion of the internal surface. The zinc content in the etching pits decreased obviously and dezincification corrosion could be classified. Some suggestions for anti-corrosion measures of the brass tubes were put forward.