首页> 外文会议>International Symposium on Aerodynamics, Ventilation and Fire in Tunnels >Cross-City-Link Zurich - Proof of proper functionality of the emergency ventilation system in the case of a fire using smoke tests, measurements and CFD simulation
【24h】

Cross-City-Link Zurich - Proof of proper functionality of the emergency ventilation system in the case of a fire using smoke tests, measurements and CFD simulation

机译:Cross-City-Link苏黎世 - 使用烟雾测试,测量和CFD仿真的火灾情况下应急通风系统适当功能的证明

获取原文

摘要

This paper presents the coupled methodology followed to prove the proper functionality of the emergency ventilation system installed for the case of a 10 MW fire in the underground railway station of the Cross-City-Link Zurich. This coupled methodology encompasses the use of a) smoke tests with reduced fire power, b) aerodynamic measurements, c) calibration of the numerical model to represent the real aerodynamic conditions and d) employing this calibrated model to simulate a 10 MW fire inside a stationary train in the station using transient 3-D Computational Fluid Dynamics (CFD) simulations for four different fire positions.
机译:本文介绍了耦合方法,遵循以在交叉城市链路苏黎世的地下火车站内安装的紧急通风系统的适当功能。该耦合方法包括使用A)烟雾测试的使用减少,B)空气动力学测量,C)校准数值模型来表示采用这种校准模型的实际空气动力学条件和D)模拟一个固定内部的10 MW火力使用四种不同的火灾位置的瞬态3-D计算流体动力学(CFD)模拟火车。