首页> 外文会议>International Conference on Renewable Energy and Environmental Technology >Economic Comparison of VSC-HVDC and HVAC Systems for Connections of Offshore Wind Farms
【24h】

Economic Comparison of VSC-HVDC and HVAC Systems for Connections of Offshore Wind Farms

机译:近海风电场连接VSC-HVDC和HVAC系统的经济比较

获取原文

摘要

Large-scale offshore wind power has been developed in recent years, and two possibilities are considered for the transmission system between the offshore wind farms and the onshore grid: VSC-HVDC and HVAC. The paper aims to compare both systems for 300MW offshore wind farms, 25 km, 50km and 75km from the Point of Common Coupling on an economic basis using a DCF(discounted cash flow) analysis. A linear fit to the net present values has been made, obtaining the break-even distance of 47km. When the transmission distance is shorter than 47km, the HVAC system is more economic, otherwise the VSC-HVDC system is a more cost-efficient option.
机译:近年来已经开发了大型海上风电,并考虑了海上风电场和陆上电网之间的传输系统的两种可能性:VSC-HVDC和HVAC。本文旨在使用DCF(折扣现金流量)分析,将300mW海上风电场,25公里,50公里和75公里的系统进行比较,从共同耦合到经济基础。已经进行了线性拟合净现值,获得了47km的断裂距离。当传输距离短于47km时,HVAC系统更加经济,否则VSC-HVDC系统是更具成本效益的选项。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号