首页> 外文会议>International Conference on Artificial Intelligence, Automation and Control Technologies >Study on Reactive Power Imbalance and Its solution of Parallel Coupled Transmission Lines
【24h】

Study on Reactive Power Imbalance and Its solution of Parallel Coupled Transmission Lines

机译:反应功率不平衡及其平行耦合输电线路的研究

获取原文

摘要

In view of the imbalance and even the abnormal phenomenon of reactive circulation of parallel high voltage transmission lines with similar measured parameters in actual operation, combined with field investigation and test, theoretical analysis and simulation demonstration, it is clear that this phenomenon is caused by the use of unconventional phase sequence and unreasonable transposition of the two-circuit lines when erecting the same tower. Based on the PSCAD simulation, the corresponding improvement measures are put forward from two aspects of optimizing the arrangement of phases and transposition. The results show that in order to solve the power imbalance problem of parallel coupled transmission lines, it is recommended to optimize the phase sequence of conductors in consideration of economy and operability.
机译:鉴于不平衡甚至是平行高压传输线的反应性循环异常现象,在实际操作中具有类似测量的参数,结合现场调查和测试,理论分析和仿真示范,很明显这种现象是由此引起的在架设相同塔时,使用非传统相序和双电路线的不合理转换。基于PSCAD仿真,从优化阶段排列和换位排列的两个方面提出了相应的改进措施。结果表明,为了解决并联耦合传输线的功率不平衡问题,建议考虑到经济性和可操作性,优化导体相序。