首页> 外文会议>CIBO Industrial Emissions Control Technology Conference >Results of hydrated lime DSI field trial tests for HCl removal from industrial coal fired boilers - (PPT)
【24h】

Results of hydrated lime DSI field trial tests for HCl removal from industrial coal fired boilers - (PPT)

机译:工业煤锅炉HCL清除水合石灰DSI现场试验结果 - (PPT)

获取原文

摘要

Emission limits required to be met for - PM, Hg, CO, HCl. About 1,100 solid fuel fired boilers affected - About 600 are coal-fired boilers. Most fire bituminous coal → requires HCl reduction - HCl limit = 0.022 lb/MMBtu - 500 ppm CI (dry) about 0.04 lb/MMBtu HCl potential: 50% HCl reduction required - 1,500 ppm Cl (dry) about 0.12 lb/MMBtu HCl potential: 80% HCl reduction required.
机译:所需的排放限制 - PM,Hg,Co,HCl。受影响的约1,100次固体燃料燃烧锅炉 - 约600是燃煤锅炉。大多数火沥青煤→需要HCl降低 - HCl Limit = 0.022磅/mmBtu - 500 ppm Ci(干)约0.04磅/mmbtu HCl电位:50%HCl减少缩减量 - 1,500ppm Cl(干燥)约0.12磅/mmbtu HCl电位:需要80%的HCL减少。