Air Change per Hour (ACH) or ventilation rate alone is typically specified in most ventilation standards. The Air Exchange Effectiveness (AEE) with which the outdoor air reaches the occupant breathing zone and provides exposure control to the occupant by effective dilution is equally important. The novel Single Coil Twin Fan (SCTF) air-conditioning and air distribution system is employed in a field aplication to evaluate the performance of three different types of air distribution systems. Despite comparable ACH values in all three scenarios, the findings clearly show that the Personalised Ventilation - Under Floor Air Distribution (PV-UFAD) and Displacement Ventilation (DV) systems result in considerably higher AEE in the occupied zones compared to the Mixing Ventilation (MV) system.
机译:单独的空气变化(ACH)或单独的通风率通常在大多数通风标准中规定。室外空气到达乘员呼吸区的空气交换有效性(AEE),通过有效稀释将暴露对乘员提供暴露控制同样重要。新颖的单线圈双风扇(SCTF)空调和空气分配系统用于现场应用,以评估三种不同类型的空气分配系统的性能。尽管在所有三种情况下都有相当的ACH值,但研究结果清楚地表明,与混合通气(MV)相比,个性化通风 - 在地板空气分配(PV-UFAD)和位移通风(PV-UFAD)和位移通风(DV)系统中导致占用区中的大幅增加。 ) 系统。