Fault Location in Unearthed 60 kV Subtransmission Network based on the Travelling Wave Method

机译:基于行波方法出土的60 kV子传输网络中的故障位置

获取原文

摘要

In this paper a single-ended travelling wave-based fault location algorithm is presented with reference to HV (60 kV) overhead unearthed operated lines: the time-frequency characteristics of the travelling wave signal are processed by utilising the phase to modal transformation and the continuous wavelet one. The frequency components of the processed signals are used for the travelling wave speed calculation whereas the time components are used for determining the wave arrival times. The fault position is evaluated by combining these two aspects. The proposed approach has been tested in different conditions, in order to assess the method stability: it has been proven insensitive to the fault position, fault resistance and the fault inception angle.
机译:在本文中,参考HV(60kV)开销出土的电路线提供了一种单端行进波的故障定位算法:通过利用阶段与模态变换和阶段进行处理的时间频特性。连续小波一。处理后信号的频率分量用于行进波速计算,而时间分量用于确定波到达时间。通过组合这两个方面来评估故障位置。所提出的方法已经在不同的条件下进行了测试,以评估方法稳定性:已被证明对故障位置,故障和故障成立角度不敏感。