首页> 外文会议>International Conference on Intelligent Transportation, Big Data and Smart City >Analysis of a Misoperation Accident of the 220kv Bus Difference Backup Protection
【24h】

Analysis of a Misoperation Accident of the 220kv Bus Difference Backup Protection

机译:220kv母线差动后备保护误动事故分析

获取原文

摘要

As the power grid continues to grow, the number of components on buses is increasing. It requires bus differential protection to integrate reliability and security. This paper has introduced the inspection and handling process of a malfunction accident of 220kV microcomputer bus differential protection. The model bus differential protection was the product after six unified. The basic principle of busbar differential backup protection has been introduced. The causes of misoperation caused by microcomputer bus differential protection are analyzed from three aspects: criterion of operation bus, generation of differential current, and rationality of operation bus voltage blocking. Preventive measures and solutions for preventing malfunction of microcomputer bus differential protection has been given in this paper. Through the suggestion of changing the logic of the criterion of the running bus and the opening of the busbar voltage, the reliability of the protector has been greatly improved and the safe and stable operation of the power grid has been ensured.
机译:随着电网的不断发展,总线上的组件数量也在增加。它需要总线差动保护以集成可靠性和安全性。介绍了一次220kV微机母线差动保护故障事故的检查与处理过程。模型总线差动保护是六个统一后的产品。介绍了母线差动后备保护的基本原理。从操作母线的判据,差动电流的产生以及操作母线电压闭锁的合理性三个方面分析了微机母线差动保护引起误动作的原因。提出了防止微机母线差动保护误动作的预防措施和解决方案。通过改变运行母线的判据逻辑和母线电压的断开的建议,保护器的可靠性得到了极大的提高,并确保了电网的安全稳定运行。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号