In presence of large disturbances, observation of separation mechanism based on wide-area measurements and emergency controls are important and problematic tasks to restore system stability. This paper proposed a novel approach to properly locate the controllers and observers based on modal analysis. For structure preserving models, rank tests are proposed to qualify the placement to ensure the unstable modes of the disturbance controllable or observable, and the corresponding mode observability and controllability matrices are utilized to sift most sensitive sites to detect system separation and most effective sites for emergency controls to act against modes of instability. With the few sites selected, crucial measurements can be singled out from large amount of system states, and emergency controls can conveniently be combined and designed for the disturbance. The proposed placement approach is verified in 10-machine New England power system.
机译:在存在大扰动的情况下,基于广域测量和应急控制的分离机制观察是重要的和有问题的任务,可以恢复系统稳定性。本文提出了一种基于模态分析正确定位控制器和观察者的新方法。对于结构保存模型,提出了级别测试,以确保扰动可控或可观察的不稳定模式,并且相应的模式可观察性和可控性矩阵用于筛选最敏感的位点,以检测系统分离和最有效的应急场所对不稳定性的控制行动。随着少数选定的网站,可以从大量系统状态挑出至关重要的测量,并且可以方便地将紧急控制能够用于干扰。拟议的放置方法是在10架新英格兰电力系统中核实。