首页> 外文会议>Structures congress >Vibrations Assessment of a Hospital Floor for a Magnetic Resonance Imaging Unit (MRI) Replacement
【24h】

Vibrations Assessment of a Hospital Floor for a Magnetic Resonance Imaging Unit (MRI) Replacement

机译:磁共振成像单元(MRI)更换医院地板的振动评估

获取原文

摘要

This is a case study where the goal is to predict the vibration environment due to a footfall excitation in the vicinity of a replacement Magnetic Resonance Imaging (MRI) unit on a hospital floor. A new MRI unit with a weight of 19,000 lbs replaces an existing, much heavier unit with a weight of 82,000 lbs. Dynamic characteristics of the floor will change when the new unit is installed, affecting the vibration environment of the unit that is generated by nearby footfalls. In this study we use physical heel drop measurements of the existing conditions to calibrate a computer model that we then use to predict the vibrations and compare the calculated vibrations with the criteria for the new unit. The results show that the vibration levels predicted for the new MRI unit do not exceed its vibration criterion. The paper will present detailed analytical model and analysis procedure, together with conclusions.
机译:这是一个案例研究,目标是预测医院地板上更换的磁共振成像(MRI)单元附近的脚步声激发引起的振动环境。重量为19,000磅的新MRI装置取代了重量为82,000磅的现有较重的装置。安装新设备后,地板的动态特性将发生变化,从而影响附近人行道产生的设备振动环境。在这项研究中,我们使用对现有条件的物理脚跟掉落测量来校准计算机模型,然后将其用于预测振动并将计算出的振动与新设备的标准进行比较。结果表明,为新的MRI单元预测的振动水平未超过其振动标准。本文将介绍详细的分析模型和分析过程以及结论。