首页> 外文会议>Structures congress >Vibrations Assessment of a Hospital Floor for a Magnetic Resonance Imaging Unit (MRI) Replacement
【24h】

Vibrations Assessment of a Hospital Floor for a Magnetic Resonance Imaging Unit (MRI) Replacement

机译:用于磁共振成像单元(MRI)替代的医院地板的振动评估

获取原文

摘要

This is a case study where the goal is to predict the vibration environment due to a footfall excitation in the vicinity of a replacement Magnetic Resonance Imaging (MRI) unit on a hospital floor. A new MRI unit with a weight of 19,000 lbs replaces an existing, much heavier unit with a weight of 82,000 lbs. Dynamic characteristics of the floor will change when the new unit is installed, affecting the vibration environment of the unit that is generated by nearby footfalls. In this study we use physical heel drop measurements of the existing conditions to calibrate a computer model that we then use to predict the vibrations and compare the calculated vibrations with the criteria for the new unit. The results show that the vibration levels predicted for the new MRI unit do not exceed its vibration criterion. The paper will present detailed analytical model and analysis procedure, together with conclusions.
机译:这是一个案例研究,其中目标是预测由于医院地板上的替换磁共振成像(MRI)单元附近的脚踏性激发导致的振动环境。具有重量19,000磅的新MRI单元取代了具有82,000磅的重量的现有,更重的单位。在安装新装置时,地板的动态特性将改变,影响由附近脚步生成的装置的振动环境。在这项研究中,我们使用现有条件的物理脚跟掉落测量来校准我们的计算机模型,然后我们用来预测振动并将计算的振动与新单元的标准进行比较。结果表明,新的MRI单元预测的振动水平不会超过其振动标准。本文将呈现详细的分析模型和分析程序,得出结论。