首页> 外文会议>International Symposium on Solid Oxide Fuel Cells >Integration of Solid Oxide Fuel Cell with Liquid Desiccant Cooling for Generation of Combined Cooling and Power for a Server
【24h】

Integration of Solid Oxide Fuel Cell with Liquid Desiccant Cooling for Generation of Combined Cooling and Power for a Server

机译:固体氧化物燃料电池与液体干燥剂冷却的整合,用于生成服务器的组合冷却和电力

获取原文

摘要

In this study the integration of a SOFC with liquid desiccant system is considered for powering and cooling a data center at the rack level. The novel idea is that each single fuel cell (~12 kW) is used to power one server rack and the waste heat from the fuel cell is used to regenerate a desiccant to provide dehumidification or cooling. The objective of this study is to theoretically investigate the capability of the integrated system to provide enough cold and dehumidified air to keep the server rack in the safe range of temperature and humidity. Results show that the SOFC waste heat can produce cold and dehumidified air within the safe range for server racks. However, with continuous outside air conditions of 25°C and 70% relative humidity the heat from the current SOFC system is enough to provide 25% of the air flow demand for each server rack.
机译:在这项研究中,考虑使用SOFC与液体干燥剂系统的集成,用于在机架电平处供电和冷却数据中心。新颖的想法是每个燃料电池(〜12kW)用于为一个服务器架电,并且来自燃料电池的废热用于再生干燥剂以提供除湿或冷却。本研究的目的是从理论上研究了集成系统的能力,以提供足够的冷和除湿空气,以保持服务器机架在安全范围的温度和湿度范围内。结果表明,SOFC废热可以在服务器机架的安全范围内产生冷和除湿空气。然而,在25°C和70%相对湿度的连续外部空气条件下,来自电流SOFC系统的热量足以为每个服务器机架提供25%的空气流量需求。