The Energy Saving Analysis of Coupled Water Source Heat Pump System Applied in Campus Building

机译:耦合水源热泵系统在校园建筑中的节能分析

获取原文

摘要

Campus buildings often consume more energy than other buildings in China,especially in operation process.Water source heat pump system as an application form of renewable energy in buildings is advocated in China.In this paper the operational principle of coupled water source heat pump is introduced,and the energy saving analysis of coupled water source heat pump from the view of design and operation is presented by field test.The operation data of heat pump system and unit was measured and collected separately in summer and winter.Then the technical performance index of heat pump unit,such as power consumption and EER,is analyzed with the variation of the temperature of well water and circulating water both in theory and from the experimental results.In addition,different control strategies matching with different running conditions in winter and summer are suggested according to the system performance analysis.
机译:校园建筑通常比中国其他建筑消耗更多的能源,尤其是在运行过程中。中国倡导将水源热泵系统作为建筑物中可再生能源的一种应用形式。本文介绍了水源热泵耦合的运行原理。并通过现场试验从设计和运行的角度对耦合式水源热泵进行了节能分析。在夏季和冬季分别对热泵系统和机组的运行数据进行了测量和收集。从理论和实验结果两方面对井水和循环水温度的变化进行了分析,分析了热泵机组的能耗和能效。建议根据系统性能进行分析。