首页> 外文会议>International Conference on Power Transmission amp; Distribution Technology; 20051011-15; >A Method of Locating and Isolation for Single Phase Grounding Fault Section of Feeders in Power Distribution Network based on Time Limit Zero-Sequence Voltage
【24h】

A Method of Locating and Isolation for Single Phase Grounding Fault Section of Feeders in Power Distribution Network based on Time Limit Zero-Sequence Voltage

机译:基于时限和零序电压的配电网馈线单相接地故障段定位与隔离方法

获取原文
获取原文并翻译 | 示例

摘要

In order to solve the problem of single phase grounding fault locating in non-effectively grounding network, this paper analyzes the character of single phase grounding fault. According to the working principle of generating line insulation supervisory devices in transformer substation, the property of line imbalance voltage, and the practical operation demand of feeder terminal unit (FTU), a method of single phase grounding fault locating for FTU, the time limit & zero-sequence voltage method, is proposed, which operates on the feeder automation system of voltage-time type. The main principle about this method is given and the operating mode how to cooperate FTU is also discussed. At last, combined with the project example of Zhongshan loop-feeder automation system, the analysis about fault insulating process is described in detail. It is pointed out that the time limit & zero-sequence voltage method is feasible and practical.
机译:为了解决单相接地故障在非有效接地网中的定位问题,分析了单相接地故障的特点。根据变电站中产生线路绝缘监控装置的工作原理,线路不平衡电压的特性以及馈线终端单元(FTU)的实际运行需求,确定FTU的单相接地故障的定位方法,时限和提出了一种零序电压方法,该方法在电压时间型馈线自动化系统上运行。给出了该方法的主要原理,并讨论了如何配合FTU的工作模式。最后结合中山市环网自动化系统的工程实例,对故障绝缘过程进行了详细的分析。指出时限零序电压法是可行的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号