首页> 外文会议>IEEE Power & Energy Society General Meeting >Galloping amplitude analysis and observation on full-scale test overhead transmission lines
【24h】

Galloping amplitude analysis and observation on full-scale test overhead transmission lines

机译:满载测试架空输电线路的舞动幅度分析与观察

获取原文

摘要

Conductor galloping seriously threatens the safety operation of power transmission lines, especially for the compact transmission lines with small distance between phase conductors. The conductor galloping maximum amplitude is an important parameter for transmission line inter-phase short circuit failure analysis. In this paper, a single degree freedom model is employed to analyze the relationship between the conductor galloping amplitude and its impact factors. The impacts of wind velocity, the loops of galloping and the conductor span on the galloping amplitude are then analyzed. Experimental investigation of conductor galloping is carried out on full-scale test overhead transmission lines. The observation results validated the theoretical analysis conclusions.
机译:导体的疾驰严重威胁着输电线路的安全运行,特别是对于相线之间距离很小的紧凑型输电线路。导体疾驰的最大振幅是传输线相间短路故障分析的重要参数。本文采用单度自由度模型来分析导体驰豫幅度及其影响因素之间的关系。然后分析了风速,舞动回路和导体跨度对舞动幅度的影响。导体驰gall的实验研究是在全面测试架空输电线路上进行的。观测结果验证了理论分析结论。