摘要

This paper,in the view of indoor security,analyzes the leak variation and indoor R32 concentration distribution when it leaks from the running indoor unit using experimental method.The results show that the leak rate of R32 decreases with the air conditioner operating.And the leak process of refrigerant under operating conditions can be classified into two stages,fast leak stage and slow leak stage.The concentration of test points increases at first,then decreases and gradually stabilizes.Near the leak hole,it is the highest and varies dramatically.And it is high in the supply air mine stream,but it is only about 15% of the LFL.The concentration of the corner that the air supply cannot reach is the lowest.The indoor security during the leaking process of R32 is evaluated,and the results show that the combustible zone only appears near the leak hole,and its duration is very short.Ignition experiment was taken in the combustible region and the results show that the candle flame and spark diffuse slightly,but it can not spread effectively.It can be concluded that the hazard of using R32 as the refrigerant of air conditioner is low when the air velocity and angle were keeping at 5.8m/s and 25°.In order to improve the security of the indoor environment further,this paper also analyzes the impact of exhaust on indoor R32 concentration distribution and the results indicate that ventilation can reduce indoor R32 concentration effectively.Thus,it can reduce the risk of fire by opening the exhaust fan when R32 leaks with the air conditioner running.
机译:本文从室内安全的角度,通过实验方法分析了从运行中的室内机泄漏时的泄漏变化和室内R32的浓度分布。结果表明,R32的泄漏率随空调的运行而降低。工作条件下的制冷剂过程可分为快速泄漏阶段和缓慢泄漏阶段两个阶段。测试点的浓度先升高,然后降低并逐渐稳定。在泄漏孔附近,它是最高的并且变化很大。空气供应量较高,但仅为LFL的15%左右。空气供应无法到达的拐角处的浓度最低。评估了R32泄漏过程中的室内安全性,结果表明可燃区仅出现在泄漏孔附近,持续时间很短。在可燃区进行了点火实验,结果表明蜡烛的火焰和火花可以得出结论,当风速和角度分别保持在5.8m / s和25°时,将R32用作空调制冷剂的危险性较低。为了进一步提高室内环境的安全性,本文还分析了排气对室内R32浓度分布的影响,结果表明通风可以有效降低室内R32浓度。因此,R32泄漏时打开排气扇可以降低火灾危险。在空调运行的情况下。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号