摘要

This paper presents the results of analyses of the effectiveness of a superconducting fault current limiter (SFCL) to stabilize the synchronous generators, suppress turbine shaft torque oscillations, and limit the fault current in a two-machine-infinite bus system. In this study, the system model with two SFCLs having shunt resistance installed at each generator terminal was used taking 3LG (three lines to ground) fault at 12 fault points into account. These analyses were performed using EMTP/ATP. It is concluded that the use of SFCL with shunt resistance value of 1.1 pu is most effective for all fault points for the stabilization of synchronous generators, the suppression of turbine shaft torque oscillations, and the limitation of fault current.
机译:本文介绍了分析超导故障限流器(SFCL)在两机无穷大母线系统中稳定同步发电机,抑制涡轮轴转矩振荡以及限制故障电流的有效性的分析结果。在本研究中,使用在每个发电机终端安装两个带有并联电阻的SFCL的系统模型,并考虑了12个故障点处的3LG(接地三线)故障。这些分析是使用EMTP / ATP进行的。结论是,对于所有故障点而言,使用分流电阻值为1.1 pu的SFCL对同步发电机的稳定,抑制涡轮轴转矩振荡以及限制故障电流最为有效。