Considering the damage mechanism of oil-impregnated paper insulation in power transformers, shunt reactors and other high voltage electrical apparatus caused by partial discharge, a concept of “destructive partial discharge” is introduced in this paper. The intensity of this discharge is regarded as several thousands pico-coulomb (pC) and may cause the insulation a fatal damage. An oil-paper insulation is usually able to withstand this type of partial discharge for a period of time prior to failure. This provides engineers a time window to detect it. This paper describes an on-line partial discharge monitoring system for 500kV shunt reactors. The commission results from 3 single-phase shunt reactors either connected or disconnected to the grid showed that the on-line partial discharge detecting system has a high noise immunising ability. Two years later after the installation, a pre-warning signal was received from one shunt reactor indicating the existence of an intermittent discharge. The acoustic emission system located its position at the low end of the high voltage bushing in the oil. Dissolved gasses analysis (DGA) in the oil suggested the presence of partial discharge, as acetylene (C2H2) was as high as 20ppm. PD activity was further confirmed by a physical examination on the reactor.