Air conditioning using an air-cooled single effect lithium bromide absorption chiller: Results of a trial conducted in Madrid in August 2005

机译:使用风冷单效溴化锂吸收式制冷机的空调:2005年8月在马德里进行的试验结果

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Trials were conducted to determine the performance of a commercial (Rotartica 045v) 4.5-kW air-cooled, single effect LiBr/H2O absorption chiller for residential use. The experiments were run at La Poveda, Arganda del Rey, Madrid, in August 2005. Three typical August days, with different outdoor temperatures, were chosen for the study. The hot water inlet temperature in the generator varied throughout the day from 80 to 107 °C. Thermal demand was calculated, along with period energy balance and COP. Variations in machine component temperatures were recorded and chilling power and the daily COP calculated for each of the three days. The results for the period as a whole showed that cooling power tended to decline with rising outdoor dry bulb temperatures. At temperatures from 35 to 41.3 °C the chilled water outlet temperature in the evaporator climbed to over 15 °C. The average COP for the period, when auxiliary equipment was included into the calculations, was 0.37.
机译:进行了试验以确定商用(Rotartica 045v)4.5 kW风冷单效LiBr / H2O吸收式制冷机的性能。该实验于2005年8月在马德里Arganda del Rey的La Poveda进行。研究选择了三个典型的8月天,不同的室外温度。发生器中的热水入口温度全天在80至107°C之间变化。计算了热需求,以及周期能量平衡和COP。记录机器部件温度的变化,并计算三天中每一天的制冷能力和每日COP。整个时期的结果表明,随着室外干球温度的升高,冷却能力趋于下降。在35至41.3°C的温度下,蒸发器中的冷却水出口温度攀升至15°C以上。如果将辅助设备包括在计算中,则该期间的平均COP为0.37。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号