首页> 美国政府科技报告 >Ground Fault and Overcurrent Protection Criteria for Coal Mine AC Distribution Systems
【24h】

Ground Fault and Overcurrent Protection Criteria for Coal Mine AC Distribution Systems

机译:煤矿交流配电系统接地故障及过流保护判据

获取原文

摘要

Ground fault and overcurrent protection criteria for coal mine ac distribution systems were examined by authorization of the Bureau of Mines. The report begins with a literature review that discusses relaying topics including instrument transformers, ground fault pickup methods, static relaying, and comparison of relaying techniques. A chapter on ground fault relaying provides recommendations for maximum and minimum pickup levels as a function of maximum ground current and power system line-to-ground capacitance. Research in the area of phase overcurrent protection has resulted in a complete set of procedural recommendations for the selection and setting of overcurrent relays and current transformers, molded-case circuit breakers, and distribution system fuses in coal mine power systems. The final chapter discusses relay system maintenance and introduces a unique test set that is used to test the performance of relaying systems in coal mines.