Suppression of Gas Well Blowout Fires Using Water Sprays; Large and Small Scale Studies. Presented at American Petroleum Institute, Committee on Fire and Safety Protection, Production Session, Hyatt Regency, San Antonio, Texas, September 11-13, 1984.

机译:使用喷水器抑制气井井喷火灾;大型和小型研究。 1984年9月11日至13日在德克萨斯州圣安东尼奥市的美国石油学会,消防和安全保护委员会,生产会议,凯悦酒店举行。

获取原文

摘要

Large scale simulation tests were conducted to demonstrate the effectiveness of water spray systems to control and extinguish gas well blowout fires. Selected results from small scale experiments performed in this research program are given primarily to help explain the development of the water spray extinguishment method, but also to examine scaling of important phenomena. Two techniques of water spray injection, internal and external to the initial gas jet, were tested at large scale on fires with heat release rates from 144 megawatts (138 SCFS methane flow) to 222 megawatts (212 SCFS methane flow). Using external water injection from four nozzles surrounding the gas jet, fires of almost 200 megawatt size could be extinguished with a mass flow ratio (water/gas) of 2.17 (129 GPM water flow) and continued to burn at a ratio of 1.56 (86 GPM water flow). This technique of water injection could be the basis of a practical blowout fire suppression system.