Multiple-Zone Variable Refrigerant Flow System Modeling and Equipment Performance Mapping.

机译:多区域可变制冷剂流量系统建模与设备性能映射。

获取原文

摘要

We developed a variable refrigerant flow (VRF) vapor compression system model, which has five indoor units, one outdoor unit and one water heater. The VRF system can run simultaneous space conditioning (cooling or heating) and water heating. The indoor units and outdoor unit use fin-and-tube coil heat exchangers, and the water heater uses a tube-in-tube heat exchanger. The fin-and-tube coil heat exchangers are modeled using a segment-by-segment approach and the tube-in-tube water heater is modeled using a phase-by-phase approach. The compressor used is a variable-speed rotary design. We calibrated our model against a manufacturer s product literature. Based on the vapor compression system model, we investigated the methodology for generating VRF equipment performance maps, which can be used for energy simulations in TRNSYS and EnergyPlus, etc. In the study, the major independent variables for mapping are identified and the deviations between the simplified performance map and the actual equipment system simulation are quantified.