The procedure for evaluating the electrostatic prefilter includes the steps for conducting five different tests: evaluating (1) the HEPA filter alone, (2 and 3) the HEPA filter with a standard prefilter treated both as disposable and reusable, and (4 and 5) the HEPA filter with the electrostatic prefilter, again treated as disposable and reusable. Procedures for flow-meter calibrations and measurements of particle-size distributions are also included. Long-term maintenance of the system during the evaluation program is outlined, and estimates of component durability are given. An electrical engineering safety note describes the high-voltage operational hazard of the electrostatic prefilter and the testing of safety devices (the current-overload trip circuit, the filter-door-interlock system, and the current-limiting resistor).