首页> 美国政府科技报告 >Partial Discharge Testing of Bulk Transformer Oil
【24h】

Partial Discharge Testing of Bulk Transformer Oil

机译:散装变压器油局部放电试验

获取原文

摘要

The generation of partial discharges in bulk transformer oil has been investigated experimentally to determine the dominant conditions which contribute to their formation and growth under repetitive impulse stresses. The motivation for conducting these experiments arose from a problem with partial discharges and breakdowns occurring in the insulating oil around the high voltage switch in a continuous running 1.5 MV repetitive pulser system. From the experiment it was found that repetitive stressing caused low level field ionization around the electrodes which led to bubble formation and eventually partial discharges. There were also qualitative indications of charge accumulation in the oil. Photographic records of numerous shot sequences were used to study the phenomena. (ERA citation 06:023459)