首页> 美国政府科技报告 >Measurement of Air Exchange Rates in Residential and Commercial Buildings in the Northwest: Techniques and Results
【24h】

Measurement of Air Exchange Rates in Residential and Commercial Buildings in the Northwest: Techniques and Results

机译:西北地区住宅和商业建筑的空气交换率测量:技术和结果

获取原文

摘要

In a study of air exchange rates in commercial and residential buildings, several techniques were employed to measure the air exchange: analysis of sulfur hexafluoride tracer gas decay using a portable gas chromatograph; analysis of carbon monoxide decay using a continuous infrared analyzer; analysis of nitrogen oxides decay using a continuous oxides of nitrogen analyzer; and analysis of perfluorocarbon tracer (PFT) gas using a programmable automatic sampler, and a passive capillary tube sampler. Using sulfur hexafluoride tracer gas with real-time chromatography was the most labor-intensive method, requiring constant attention for several hours; whereas, analyzing the decay of PFT tracer gas using small capillary tubes required little setup time and virtually no attention. However, the analysis of tracer gas captured by the capillary tubes was difficult and was performed using special analysis equipment. The air exchange rate measured in the commercial buildings ranged from 5 to 0.04 air changes per hour (ACH) depending on the type of heating, ventilation, and air conditioning (HVAC) system. Air exchange in the residential structures ranged from about 1 ACH to about 0.3 ACH. 6 refs., 5 tabs., 3 figs. (ERA citation 10:037014)

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号