Small scale tests oruan open recirculating cooling system with a cooling water flow of 10 m3/h conducted for a period of two years have shown that ozone could be a viable alternative to chlorine and other commonly used biocides. An average ozone dosage of 0.05 mg/L was applied continuously to the cooling water. Corrosion rates of copper alloy samples immersed in ozonized water were lower than the rates of samples in non-ozonized water. No corrosion was detected for the Cr-Ni steel alloys DIN 1.4306 and DIN 1.4404 as well as for titanium either in the presence or absence of ozone in water. This is ascribed to the formation of a thin protective layer in both cases.