A series of experiments are conducted to analyze and discuss ceiling maximum thermal smoke temperature and longitudinal decay along the centerline of the tunnel with different transverse fire source locations. The size of scale model tunnel is 72 m (length) x 1.5 m (width) x 1.3 m (height). Three transverse gas burner locations were considered, such as Location A (close to the wall), Location B (near the wall), Location C (centerline of the tunnel), the corresponding distance between the centerline of the gas burner and the tunnel wall are 0.2 m, 0.475 m and 0.75 m, respectively. It was found that Li model underestimates the maximum thermal smoke temperature beneath the ceiling with different transverse fire source locations. Thus a dimensionless coefficient 2 is put forward to consider the effect of different horizontal fire source location on thermal smoke temperature profile. The predictions by the modified model of this work agree well with the measured data in the maximum thermal smoke considering different transverse fire source locations. The revised thermal smoke temperature decay formula along the centerline of the tunnel is introduced, and the deduced values of coefficient K-c(down) are correlated linearly with transverse fire location. (C) 2016 Elsevier Ltd. All rights reserved.
机译:进行了一系列实验,以分析和讨论天花板最大热烟温度和沿具有不同横向火源位置的隧道中心线的纵向衰减。比例模型隧道的大小为72 m(长)x 1.5 m(宽)x 1.3 m(高)。考虑了三个横向燃气燃烧器位置,例如位置A(靠近墙壁),位置B(靠近墙壁),位置C(隧道的中心线),燃气燃烧器的中心线和隧道壁之间的对应距离分别为0.2 m,0.475 m和0.75 m。结果发现,Li模型低估了不同横向火源位置时天花板下方的最大热烟温度。因此,提出了无因次系数2来考虑不同水平火源位置对热烟温度曲线的影响。考虑到不同的横向火源位置,这项工作的改进模型所做的预测与最大热烟气中的实测数据非常吻合。引入了沿隧道中心线修正的热烟温度衰减公式,推导的系数K-c(down)与横向火场位置呈线性关系。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号