首页> 外文期刊>日本冷凍空調学会論文集 >Suppression of ice formation around a cooled tube using liquid-fluidized bed (further report: evaluation of ice layer as thermal resistance)
【24h】

Suppression of ice formation around a cooled tube using liquid-fluidized bed (further report: evaluation of ice layer as thermal resistance)

机译:使用液流床抑制冷却管周围的冰形成(进一步报告:冰层评估为热阻)

获取原文
获取原文并翻译 | 示例
           

摘要

An experimental study was performed on ice formation around a brine-cooled tube embedded horizontally in a liquid-fluidized bed. It was found that the ice layer thickness evaluated from thermal resistance, equivalent thickness, is thinner than the actual average thickness, and that the ratio of the equivalent to the average thickness depends on a non-dimensional parameter consisted of Biot number and cooling temperature ratio for liquid single-phase flow, and additionally of the Archimedes number for liquid fluidized bed.
机译:在水平流化床中水平嵌入的盐水冷却管周围进行实验研究。 发现从热阻,等效厚度评价的冰层厚度比实际平均厚度更薄,并且相当于平均厚度的比率取决于由Biot数和冷却温度比组成的非尺寸参数 对于液体单相流,并且另外的液体流化床的前型数量。